Abstract:Accurate harmonic analysis is an important prerequisite of harmonic pollution control and power quality improvement.In IEC 61000-4-7 standard,the harmonic group method is recommended for harmonic measurement in the case of nonsynchronous sampling.While for inter-harmonics measurement,it makes great simplification and is unable to get the accurate information of inter-harmonic frequency and amplitude.Aiming at this problems,an improved method based on IEC standard and spectrum estimation combined with PSO can realize accurate detection of harmonics and inter-harmonics.Due to the fact that the content of harmonics in actual power grid is much larger than that of the inter-harmonic components,and their frequencies are relatively fixed,firstly,the parameters of fundamental and harmonic components are estimated accurately by using the “harmonic group” method recommended by IEC standard.Secondly,after the fundamental and harmonic components are filtered out,the output voltage signal is reconstructed in time domain,and high precision spectrum analysis is conducted for the reconstructed inter-harmonic signal by using spectrum estimation theory,the frequency and amplitude parameters of interharmonics is obtained by combining PSO method.This improved method can detect inter-harmonics components adjacent to the harmonics and significantly reduce the influence of harmonics on inter-harmonics.Simulation results based on Matlab verify the effectiveness of the algorithm.