Real-time Detection of Amplitude and Phase of Fundamental Wave Considering the Decaying DC Component
ZHANG Jianxin,XIE Lirong,DU Liwei,LIU Lei
DOI: https://doi.org/10.13234/j.issn.2095-2805.2023.2.129
2023-01-01
Abstract:The transient faults in power systems are prone to generate interference signals such as transient decaying DC component(DDC) and high-order harmonics. Therefore, the effective filtering of interference signals for fast and accurate amplitude and phase detection of voltage fundamental wave is important for improving the power quality. To this end,based on the periodicity and half-wave symmetry of the three-phase distorted voltage signal, it is suggested that the sampling should be delayed by a half period and a full period respectively for the distorted voltage under the abc coordinate system, thus realizing the detection of DDC during a unit cycle. Then, for the distorted voltage signal containing DDC and high-order harmonics simultaneously, the DDC detection algorithm is combined with the moving average filter algorithm under the dq rotating coordinate system, so that both the DDC and high-order harmonics can be filtered out simultaneously during the unit cycle. Finally, the proposed detection algorithm is combined with the voltage phase open-loop detection algorithm, and an RT-LAB hardware-in-the-loop realtime simulation platform was built to verify the amplitude and phase detection of voltage fundamental wave. Experimental results show that the response time of the proposed detection algorithm, which filters out the DDC and high-order harmonics under the dq coordinate system simultaneously, was only 20 ms, showing the effectiveness of the proposed algorithm and the correctness of analysis results.