Study on Protective Function Test of Control Unit of Thyristor Level in HVDC Converter Valve Based on Thyristor Reverse Recovery Characteristics

LIU Longchen,YUE Ke,PANG Lei,ZHANG Xinghai,LI Yawei,ZHANG Qiaogen
DOI: https://doi.org/10.13335/j.1000-3673.pst.2017.0249
2017-01-01
Abstract:In order to master in-situ protective firing test technology of control unit of thyristor level in converter valve, reverse recovery characteristic test circuit of high power thyristor was built and effects of forward current amplitude on reverse recovery characteristics of thyristor were studied experimentally under power frequency. Results show that reverse recovery time increases exponentially with rise of the forward current and tends to be saturated, and its saturation value is abouttrr≈1020μs. Protection function test of thyristor control unit (TCU) is closely related to maximum value of the reverse recovery time. According to the reverse recovery time of thyristor, time parameter of transient test pulse output by impulse power supply in synthetic test system of thyristor level is set to test protective fuction of TCU. For LV protective firing test of TCU reverse recovery period, LV test pulse should be output to thyristor level attr+50μs (1070μs); for HV protective firing test of TCU reverse recovery period, HV transient pulse should be output to thyristor level at 1.2trr (1224μs). Results of TCU protection function test show that the time parameter setting of the test pulse is effective and reasonable.
What problem does this paper attempt to address?