A ONE TERMINAL TRANSIENT ENERGY BASED FAULTY PHASE SELECTION METHOD FOR PROTECTION OF DOUBLE CIRCUIT LINES

YANG Ying,YU Wei-yong,TAI Neng-ling
DOI: https://doi.org/10.3321/j.issn:1000-3673.2005.13.013
2005-01-01
Abstract:When fault occurs in double circuit transmission line, it is very important for system operation to trip out the faulty phase and it is necessary to judge the faulty phase in the double circuit. On the basis of fault component, the energy information of high frequency current caused by the fault is analyzed by the modal transform. Because the modal components caused by various kinds of faults as well as the corresponding features of modal components are different, so the relation between the modal energy functions and the fault kinds are built and a new faulty phase detection method, which needs only the current information at one terminal and does not require the communication between the two terminals, is proposed. The simulation results by EMTP verified the correctness of the proposed method.