New Algorithm for Random Harmonic Current Detection in Three Phase Four Wire System

ZHOU Lin,LI Qiu-hua,ZHANG Feng
DOI: https://doi.org/10.3969/j.issn.1003-6520.2007.11.034
2007-01-01
Abstract:Active Power Filter is an important device to eliminate the pollution of harmonic,the key problem in APF is to detect the harmonic current accurately in real-time mode.Separate usage of APF needs a lot of investment early and its running efficiency is low,so APF should be used with PF,but this kind of APF needs to detect the random harmonic current.In this paper a new detection algorithm for random harmonic current in three-phase four-wire system is presented.This algorithm which is based upon the traditional ip-iq method can detect positive and negative sequence component of random harmonic current respectively by properly modifying the switch matrix,also can detect the zero sequence current component by certain equivalent triangle conversion of the phase current's zero sequence component.Finally the detected positive,negative and zero phase sequence can be summed up to obtain the random harmonic current.This algorithm conquers the localization that the method of ip-iq can only be used in the harmonic detection in the system of three-face three-wire.This algorithm can be used not only in the random harmonic detection in asymmetry three-face three-wire system but also in the three-face four-wire system,so it has biggish practical value.The algorithm has a high precision and high stability.Analysis and simulation prove the correctness of the algorithm.
What problem does this paper attempt to address?