Study on Partial Discharge Characteristic in XLPE Accessory Based on Pulse Sequence Analysis

Lu Pu,Hui Ni,Xuefeng Zhao,Zeli Ju,Junbo Deng,Guanjun Zhang
DOI: https://doi.org/10.16790/j.cnki.1009-9239.im.2016.12.009
2016-01-01
Abstract:The partial discharge characteristics of defects in cable accessory were characterized by PSA. Three kinds of typical defects were designed in cable accessory, and a partial discharge detection plat-form based on pulse current method was built. The cable accessory was carried out step-up voltage exper-iment and long-time withstand voltage experiment, and the PSA pattern and PRPD pattern of defects in XLPE cable accessory were compared. The results show that the PSA pattern can describe the pulse sequence characteristics of partial discharge as a supplement of traditional PRPD pattern. It can distin-guish the defect types of cable accessory better and has important reference value for early warning breakdown of cable accessories. The probability density can be used as a characteristic parameter of PSA pattern in partial discharge detection.
What problem does this paper attempt to address?