Analysis of transformer noise frequency spectrum under short-circuit and no-load conditions

Juan MO,Xia ZHANG,Jiansheng YUAN
DOI: https://doi.org/10.3969/j.issn.1003-3076.2015.02.014
2015-01-01
Abstract:By the measurement of transformer noise in the short circuit and the no?load tests in the transformer plant, the frequency spectrum and range are analyzed in this paper. The short circuit noise produced mainly by the windings and the no?load noise mainly by the iron core have obvious difference in the noise frequency. The short circuit noise only appears on the 100 Hz frequency point and the other one distributes in 100~600 Hz frequency range. On the basis of the characteristics of the frequency spectrum, the noise in different load conditions, when the transformer works in the power station, can be calculated or predicted by the method of frequency point synthe?sis. This prediction method can solve the problem that the noise of transformer in rate load operation condition can?not be obtained in the transformer plant, since there is no enough power to test and measure the transformer in full load condition in the plant.