Feasibility assessment on vacuum insulated switchgear

Yonggang Guan,Weidong Liu,Yuanxiang Zhou,Xavier Godechot
2007-01-01
Abstract:To find feasible alternatives to the use of SF6 in medium voltage switch-ear equipment, AREVA T&D and Tsinghua University has started a cooperation to investigate the feasibility of using vacuum. This paper focused on three main points of the design of the Vacuum Insulated Switchgear (VIS): the maintainability of vacuum system, the insulation performance, and the thermal behavior under operating conditions. In our work, such steps were followed: literature review, basic designs, calculation and analysis. The investigation results showed the feasibility of 40.5 kV/2 kA VIS, assuming that the thermal design and material choice are done carefully in order to fulfill the requirements: insulation rating, life time and rated current. Whereas, for High Voltage switchgear equipment, 126kV or higher voltage level, further experimental research work is still needed.
What problem does this paper attempt to address?