Evaluation and optimization of electric field on a high-voltage switchgear in nuclear power station

Tao Sun,Ling Li,Guoping Li,Shuji Yang,Wei Wang
DOI: https://doi.org/10.1007/s00202-021-01262-0
IF: 1.63
2021-03-23
Electrical Engineering
Abstract:Safety of electric power systems depends heavily on distribution of electric field in high-voltage switchgear. Switchgear failure can lead to fatal disasters in important systems. It is necessary to evaluate electric field and insulation performance for high-voltage switchgear in key systems. In this paper, considering a high-voltage switchgear system designed for nuclear power station, a three-dimensional finite element model is developed for the whole system. Distribution of electric field is simulated under different loads, including the specified voltage and the overload. The insulation property of the switchgear system is then evaluated. Experiment on the physical prototype validates the simulation evaluation. To make the electrical field well distributed and reduce peak value, method of orthogonal experiment is used for parameter design. Optimization and improvement are then proposed. The optimization results show that the reliability is improved and the electric field is well distributed. The numerical model is established on personal computer, while it is solved remotely on High Performance Computing Center. Corresponding modeling techniques and computing methods are provided in this paper.
engineering, electrical & electronic
What problem does this paper attempt to address?