Technical Feasibility of High Voltage Vacuum Insulated Switchgears

GUAN Yonggang,LIU Weidong,ZHOU Yuanxiang,XU Guozheng,DU Ning,NIE Qiong,ZHENG Xin
DOI: https://doi.org/10.16511/j.cnki.qhdxxb.2010.05.008
2010-01-01
Abstract:Vacuum is promising to substitute SF6 in high voltage switchgears.This paper focuses on the feasibility of using vacuum as the primary insulation medium in a vacuum insulated switchgear(VIS).The vacuum system maintainability,insulation performance and heat dissipation were investigated based on the literature review,construction design,and simulation.The results show that a 72.5 kV/2 kA VIS with a vacuum maintenance life of 20 years is technically feasible at current technology level,without on-site vacuum pumps and unconventional cooling measures.
What problem does this paper attempt to address?