Two-Terminal Fault Location of Monopolar Earth Fault in HVDC Transmission Line

KANG Lihong,TANG Kunming,LUO Jian,XU Ruilin,HUANG Jinhai
DOI: https://doi.org/10.13335/j.1000-3673.pst.2014.08.039
2014-01-01
Abstract:Based on time domain distributed parameter model of high voltage direct current (HVDC) transmission line, in which the influence of multistage distance infinitesimal is considered, a two-terminal fault location method for monopolar earth fault occurred in HVDC transmission line is proposed. The particle swarm optimization (PSO) algorithm is used to search the distance corresponding to the minimum voltage distribution difference value along the transmission line, such a distance is the very fault distance. To facilitate higher derivation and to smooth the disturbance in signal, the Levenberg-Marquardt method is utilized to fit transient fault data of HVDC transmission line. Comparing fault location results by the proposed method with those by Bergeron model, it is shown that the proposed method makes a lower request on sampling rate and its noise immunity is strong and the fault location method is not affected by transition resistance and fault position, so using the proposed method it is possible to implement accurate fault location within the full length of HVDC transmission lines.
What problem does this paper attempt to address?