A High-speed Protection Scheme for HVDC Transmission Line Based on Hausdorff Distance Comparison
ZHAO Hang,LIN Xiangning,YU Kun,LI Hao,CHEN Le,LI Zhengtian,WU Tonghua,GUO Zhiquan
DOI: https://doi.org/10.13334/j.0258-8013.pcsee.170102
2018-01-01
Abstract:Existing high voltage direct current transmission line traveling-wave protection has dead zone,and longitudinal differential protection serves as backup protection because it cannot avoid distributed capacitive current.The similarity between aerial mode voltage traveling wave at rectifier side and inverter side was derived in this paper:there is a great discrepancy between the waveforms at two side when an internal fault occurs,there is a high similarity when an external fault occurs.Therefore,a high-speed primary protection scheme for HVDC transmission line based on Hausdorff distance comparison was proposed,which introduced scanning method to align the waveforms at two sides,then their correlation was analyzed,and Hausdorff distance was used as the protection criteria,this scheme can eliminate the influence of distributed capacitive current.Finally,a model was constructed on PSCAD to verify the proposed protection scheme,and the simulation results shows that this protection is of high reliability.Besides,it has a low requirement for time precision,an outstanding ability to resist the transmission resistance grounding,noise and abnormal data.In some scenarios when a fault occurs at the dead zone of the lines,the proposed protection can lock the existing traveling wave protection,preventing it from malfunctioning.