Abstract:The precise fault location of HVDC transmission line is of great significance and practical engineering value.This paper introduces the double-pole HVDC transmission system and the double terminal traveling-wave fault location method which is based on the wavelet modulus maximum theory.The wavelet transform simultaneously has the good attribute of showing partial signal in the time domain and the frequency domain,and the ability of eliminating noises.The signal singular point contains most important information,and the Wavelet Modulus Maxima can portray the signal singular point and the irregularity of traveling-wave.A double-pole HVDC system is simulated by the PSCAD and MATLAB software,and the figures of the fault current traveling-wave for the negative pole and the positive pole are got.It can be analyzed that the positive pole is the fault pole from the figures.The wavelet transform figures of the rectifier traveling wave and inverter traveling wave for the fault pole are portrayed.From the wavelet transform figures,we can easily find the precise time of the initial current traveling-wave head that arrives at both sides of the bus.Then,the distances between the fault location and the both sides of the bus are computed.The result indicates that picking-up the high frequency transition signal with the wavelet transform the fault pole can be found and the initial current traveling-wave head can be distinguished accurately.Therefore,the accurate fault location of double-pole HVDC transmission system is realized.