A Fault Location Method For Hybrid Three-terminal Transmission Line

Shuping Gao,Yuanyue Jiang,Guobing Song,Yue Gao,Zixuan Zeng
DOI: https://doi.org/10.1109/IFEEA51475.2020.00065
2020-01-01
Abstract:The fault location of DC transmission lines is of great value to improve the reliability of power supply and maintain the safety and stability of the system. Therefore, accurate and reliable fault location methods are particularly important. Aiming at the problems of hybrid three-terminal dc transmission system, such as complex structure and difficult line fault location, a wavelet packet energy spectrum location method combined with BP neural network is proposed. The strategy is as follows: first, the fault line is quickly selected after the fault occurs. And then use wavelet packet to decompose and reconstruct the voltage components collected at the measurement point to obtain the wavelet packet energy. Finally, the wavelet packet energy is substituted into BP, and the corresponding fault distance can be obtained. The algorithm has high location accuracy, can be implemented easily in hardware.
What problem does this paper attempt to address?