Transmission Line High-impedance Fault Modeling Analysis for Single-end Fault Location

SUN Yueqin,NI Jiang,WANG Bin,XIE Min,WANG Haigang
DOI: https://doi.org/10.7500/AEPS20151204004
2016-01-01
Abstract:High-impedance ground faults on high-voltage transmission lines are mostly accompanied by arc discharge.The traditional Cassie and Mayr dynamic arc models are described with arc differential equations,while the numerical solution of every moment arc voltage should be calculated with iterations,hence these models cannot be directly used in relay protection and fault location.For lack of an accurate dynamic arc model,the model is generally considered a static resistant or steady arc voltage square wave model,and that results in loss of the most valuable dynamic characteristic.To solve this problem,based on the air discharge nature description of the Thompson theory,the directional movement of a large number of electrons is used to represent arc current;and the coupling relation between electric field and electronic avalanche motion in air space is utilized to create a function of arc voltage and current,thus establishing a dynamic arc model of high-impedance ground faults for the application in single terminal fault location in transmission lines.The traditional arc differential equations are complex to calculate and hard to be directly applied in current fault location and relay protection algorithms.Nevertheless,the model has overcome the defects and laid the foundation for high-impedance ground fault detection,protection and location.