Evolution Process and Severity Assessment of the Partial Discharge Caused by Immobilized Metal Particles on DC GIL Insulator Surface

Jianbo LI,Wensheng GAO,Weidong LIU
DOI: https://doi.org/10.13296/j.1001-1609.hva.2018.05.002
2018-01-01
Abstract:Immobilized metal particles on DC GIL insulator surface significantly reduce the flashover voltage on the insulator surface,which is a common defect in DC GIL. To study the evolution process and severity assessment of partial discharge caused by immobilized metal particles on DC GIL insulator surface,we established a 220 kV GIL equipment platform. By gradually increasing voltage and then using the ultraviolet viewer observed the entire partial discharge evolution process on insulator surface. Meanwhile,analyzed the average amplitude and time interval of partial discharge. The results show that:the severity of partial discharge caused by the immobilized metal particles in the insulator surface of the GIL can be classed into three levels: mild discharge,moderate discharge and severe discharge;as the discharge process intensified,the average amplitude and time interval of partial discharge followed the change. The statistical parameter Sk/Ku of average amplitude and time interval of partial discharge can be used to evaluate the severity of the defect caused by immobilized metal particles on DC GIL insulator surface.