Discharge Characteristics and Harmfulness of Millimetre Metal Particles on the 1100 Kv Insulator Surface

X. Li,Y. Xu,W. Liu,K. Zhao
DOI: https://doi.org/10.1049/icp.2022.0441
2021-01-01
Abstract:The metal particle on the insulator surface is considered to be an important factor of insulator failures in the GIS/GIL. Studying the partial discharge (PD) characteristics and harmfulness of metal particles on the insulator surface will be helpful in improving the security and reliability of the equipment. In this study, an experiment platform for the 1100-kV insulator with a high-sensitive PD detection system was established. Then the PD characteristics provoked by metal particles ( D =0.5 mm, L = 0.8, 2, 5, and 8 mm) at different positions on the 1100-kV insulator surface were investigated. The PD level as well as the harmfulness of metal particles on the insulator surface were discussed. The experimental results show that the apparent charge of the PDs provoked by metal particles shorter than 5 mm is lower than 1 pC under routine PD test condition, which will make the traditional PD detection methods ineffective in detecting these small metal particles on the insulator surface. However, it is noted that even the 5-mm-long metal particle will induce flashover and is a serious threat to the equipment. These results are expected to be helpful for condition monitoring and risk assessment of the GIS/GIL equipment.
What problem does this paper attempt to address?