Comparison on DC Icing Flashover Performance of Porcelain, Glass, and Composite Insulators

Ze XIANG,Xingliang JIANG,Zhijin ZHANG,Qin HU,Bingbing DONG,Yaoxuan WANG
DOI: https://doi.org/10.13336/j.1003-6520.hve.2014.02.015
2014-01-01
Abstract:The electrical performance of insulators in freezing condition is a basis for selecting external insulation of transmission lines and substations in icing regions. However, little research has been dedicated to the comparison between composite, porcelain and glass insulators in their DC icing flashover performances. Therefore, we analyzed these performances on the basis of a number of experiments carried out in an artificial climate chamber. The results indicate that, in severe icing condition, compared porcelain and glass insulators, ice-covered composite insulators have greater flashover voltage grads(FVG) but smaller characteristic exponents that characterize the influence of pollution on icing FVG. The characteristic exponents vary obviously with different salt deposit density and freezing-water conductivity. We also proposed a calculation expression for correcting the minimum DC FVG of iced insulators in single or coexisting conditions of salt deposit density and freezing-water conductivity. The results could be referred by the selection and design of transmission lines' external insulation in ice regions.