Analysis on Lightning Flashover of Neutral Point of 1 10 kV Transformer and Control Measures

HUANG Ying,TANG Bo,YU Zhanqing,ZENG Rong,QIN Yu,LI Ningzhi
DOI: https://doi.org/10.3969/j.issn.1007-290X.2015.02.016
2015-01-01
Abstract:In order to work out over-voltage on insulated neutral point of 1 1 0 kV transformer under lightning current impact, line cake model was used for modeling for 1 1 0 kV transformer winding and PSCAD software was adopted for simulating cal-culation on this model. Simulating analysis was carried out for breakdown of 1 1 0 kV transformer neutral point in Guangzhou region by using this model and the result indicates that it is not enough to prevent lightning by only installing discharge gap for transformer neutral point and the fault rate of neutral point reaches up to 0.686 times a year when lightning wave inva-ding the transformer which explains that it needs to combine other control measures for protection on the transformer neu-tral point in this region. According to simulation result,transformation measure of using 130 mm gap in parallel connection with Y1.5 W-72/1 86 typed arrester is proposed.