Simulation and Analysis of Lightning Overvoltage of 10 kV Cable on the Bridge of High-speed Railroad

Shun-chao WANG,Jin-liang HE,Wei-jiang CHEN
2011-01-01
Abstract:The lightning caused transients on the 10 kV cable on the bridge of high-speed railroad is studied in this paper. The simulation method involves two stages: 1) due to the fact that the thin-wire is present below and above the ground, a modified mesh current (MMC) method has been developed to calculate the voltage on the armor of the cable. This method is able to simulate the thin-wire structure with arbitrary geometry. The corresponding theory and the advantages of this method are also depicted in this paper; 2) the cable is simulated using the JMarti model in EMTP. The voltage on the armor of the cable is enforced as the voltage obtained in the first step. The simulation results show that the potential on the cable is generally very high. In contrast, the voltage (potential difference) between conductors inside the cable is typically not very large as long as the armor is grounded effectively in the end. However, if the armor is not grounded properly, the voltage between different layers inside the cable is extremely high and might cause the damage of the cable.
What problem does this paper attempt to address?