A new method of fault location with two-terminal data for four-parallel transmission lines on the same tower

Hao ZOU,Zhongan YU,Biao WU,Nengling TAI
DOI: https://doi.org/10.7667/PSPC151954
2016-01-01
Abstract:Based ondistributed parameter modeloftransmission lines, this paper proposes a new fault locating practical algorithm suitable for the four-circuit transmission line on the same tower differential protection device. Firstly, the transmission line parameters are carried out phase-mode transformation, independent double-ended with the positive sequence fault components are selected,andaccording to the theory of establishing a dual-port transmission line fault location equation, the accurate fault location is obtained. The method is simple and has less calculationamount, which avoids the complex process ofa generalrangingmethod, such ascalculating the hyperbolic functions,transcendental equations, Newtoniterative method and search methods. PSCAD/EMTDCsimulation results show that the algorithmhas high fault accuracy, andis immune to fault distance, transition resistance, fault type and power angle difference of double sides power sources, so it has practical value of engineering.
What problem does this paper attempt to address?