Flashover Characteristics of Post Insulators Under Fog and Haze Conditions

Liming WANG,Jianchao LI,Hongwei MEI,Ming LU,Zehui LIU,Chuyan ZHANG
DOI: https://doi.org/10.13336/j.1003-6520.hve.20190130011
2019-01-01
Abstract:To analyze flashover characteristics of post insulators under fog and haze conditions, we established an artificial salt spray simulation platform for pillar insulators. The conductivity of fog water was taken as the control variable and the 110 kV pillar insulator samples were subjected to artificial pollution tests with constant pressure lifting method. The pollution flashover characteristics of pillar insulators under different fog water conductivities including clean fog conditions were also given. At the same time, the pollution flashover characteristics of five kinds of pillar insulators with different umbrella structures under salt spray conditions were studied to illustrate different influences of equivalent diameter, umbrella structure in the presence or absence of ribs on the pollution flashover voltage of insulators. The results show that the condition of high fog water conductivity will influence the flashover voltage of insulator in a certain pollution, the pollution flashover voltage of insulator with slight contamination is obviously decreased, and the pollution flashover voltage of insulator with pollution value greater than 0.15 mg/cm2 is negligibly affected. Moreover, the equivalent diameter of the pillar insulator directly affects the creep distance utilization efficiency and the pollution flashover voltage. A smaller equivalent diameter indicates higher flashover voltage per creep distance, and insulators in the presence of ribs always perform better. © 2019, High Voltage Engineering Editorial Department of CEPRI. All right reserved.
What problem does this paper attempt to address?