A Discriminant Method of Fault Lines Based on Empirical Mode Decomposition

Ji Si,Li Tianquan,Chen Guangyu,Hao Sipeng
DOI: https://doi.org/10.1109/iicspi.2018.8690334
2018-01-01
Abstract:The application of electric power system transmission line protection based on traveling-waves or transient components suffers maloperation in case of single-phase earth fault. When single-phase earth fault happens, the system can still run for 1 or 2 hours because the phase voltage is still symmetry, and the ground current of fault phase is small. But single-phase earth fault will cause the increase of non-fault-phase’s voltage. Long time of grounding operation will easily make fault expand to two points or more earth short circuit, and even lead serious interphase short circuit fault. Therefore, in order to prevent more serious fault caused by single-phase earth fault, it is necessary to find out the fault line and ground fault lines as soon as possible. The analysis result in this paper conforms well to the meteorological observations and zero-sequence current detection data of Empirical mode decomposition (EMD). And these results provide useful reference for the discriminant method of fault line work in power system. According to the differences, the paper proposes a method identifying single-phase earth fault based on Empirical mode decomposition. AutoCAD simulation results proved the method is feasible.