Flashover Performance of Ice-covered LXY4-160 Insulator Strings Under Switching Impulse

Bingbing DONG,Xingliang JIANG,Daowei SHENG,Ze XIANG,Jun HUANG,Yao YUAN
DOI: https://doi.org/10.3969/j.issn.1003-6520.2013.01.008
2013-01-01
Abstract:To enrich the research content of ice-covered insulator flashover characteristics under switching impulses, we experimentally investigated seven units LXY4-160 glass insulator strings in a large multi-function artificial climate chamber under various conditions including dry, raining and ice-covered. Conclusions are drawn as follows: the 50% switching impulse flashover voltage of glass insulator strings under ice conditions remarkably decreases compared with that under dry or rainy conditions; the 50% switching impulse flashover voltage U50 of LXY4-160 glass insulator strings decreases with the increase of icing water conductivity; the positive voltage U50 and negative voltage U50 also decrease with the increase of ice amount. According to test results, the relationships between the 50% flashover voltage U50 and ice amount as well as icing water conductivity are obtained, respectively. Moreover, a calculation formula of U50 is also obtained in consideration of icing amount and icing water conductivity. It is proved that the deviations between test results and calculation results according to the correction formula are allowable in engineering applications.
What problem does this paper attempt to address?