Testing Method Research of Transmission Line Parameters

孙立山,刘洪臣,王晓媛
DOI: https://doi.org/10.3969/j.issn.1008-0686.2008.05.008
2008-01-01
Abstract:The traditional testing method of transmission line parameters is terminal open circuit and terminal short circuit.For the high voltage transmission line,the short circuit current is very big and does harm to electric power equipments due to terminal short circuit.In this paper,the practical testing method of transmission line parameter is presented in normal running conditions of line circuits.The testing method samples synchronously the voltage and current of transmission line terminal and starting part which is based on the benchmark time provided by Global Positioning System.The transmission line parameters may be obtained by iterative computation of transmission line equations based on Newton-Paphson's method.The validity of the method is demonstrated by Matlab simulation.
What problem does this paper attempt to address?