A Non-contact Voltage Measurement Method for Ultra-High Voltage DC Transmission Tower

Jiaming Zhang,Bing Tian,Zhong Liu,Bofeng Luo,Zejie Tan,Zhenheng Xu,Zhiming Wang,Jie Wei,Xinting Liu,Jun Hu
DOI: https://doi.org/10.1109/ei256261.2022.10116088
2022-01-01
Abstract:The traditional voltage measurement for the Ultra-High Voltage DC transmission line faces many problems such as high volume and high insulation cost. The non-contact voltage measurement method can solve those problems and improve measurement accuracy. This paper applies the Chebyshev integral method and the Gauss-Legendre integral method to the electric field inversion problem and takes the inductors as the integral interval. The errors of these methods can be less than 0.5%. The windy situation is also considered to test the sensibility of these methods, which shows that the error in the windy situation can be less than 1.5%.