Mehtod for Measuring the Electric Field under UHV/EHV DC/AC Hybrid Transmission Lines

张波,李伟
2012-01-01
Abstract:Because the the electric field around the AC and DC parallel transmission lines is a mixed field, which has both DC component and AC component, the traditional instruments can not be directly used to measure the field. Consequently, by the measurement principles of the DC electric field measuring device (rotating voltmeter) and the ion current density measuring devices (ion current board), we investigated the spectrum characteristics of the devices' output in the mixed electric field. Moreover we founded the relationship between the AC/DC electric field and the measuring devices' spectra, and presented the measurement methods for the electric field and the ion current density. The measurement and analysis on a reduced scale model show that the measurement methods are effective.
What problem does this paper attempt to address?