Effect Of Load On Zero-Sequence Current In Low Resistance Grounding System With Complex Grounding Fault

Yu Lei,Tian Bing,Lei Jinyong,Han Bowen,Wang Gang
DOI: https://doi.org/10.1109/CICED.2016.7576159
2016-01-01
Abstract:The events that a single-line fault evolves into a multi-line fault are increasing recently in China Southern Power Grid. To make matters worse, zero-sequence current is closely related to the load in fault lines particularly when a complex multi-line single-phase grounding fault (SPGF) occurs in a low resistance grounding system. In this case, the load factor must be considered, otherwise it may result in unneglectable calculation errors. Therefore, a comprehensive theory analysis on the relation between zero-sequence current and load was carried out for complex multi-line SPGF firstly. On this basis, the influence mechanism of load variation on zerosequence currents was analyzed in detail, and some general rules were revealed at last. The conclusions summarized in this paper can provide a theoretical basis for improving the performance of zero-sequence current protection.
What problem does this paper attempt to address?