Safety Performance of Large Grounding Grid with Fault Current Injected from Multiple Grounding Points

Zhang, B.,He, J.,Jiang, Y.
DOI: https://doi.org/10.1109/TIA.2015.2413965
2015-01-01
Abstract:Due to the overhead ground wires of transmission lines or the transformer’s neutral point connected to substation grounding grid, it looks like that there are many currents injected into or drawn out of the grounding grid from different grounding points when fault occurs. As the grounding grid is becoming larger and larger in area, the potential difference within the grounding grid may become obvious, and the assumption that the grounding points can be regarded as one point may not be suitable. This paper proposes a method to analyze the non-equipotential grounding grids with the fault current injected from multiple grounding points due to the overhead ground wires of transmission lines or the transformer’s grounded neutral point. With the method, the influences of the grid area, soil resistivity, material of the grid conductor, and relative position of the grounding points on the performance of grounding grid are thoroughly analyzed.