Voltage Dependence Measurement of A 110 Kv Lve-Tsvt

Haiming Shao,Feipeng Lin,Bo Liang,Huanghui Zhang,Wei Zhao,Jiafu Wang,Chuansheng Li
DOI: https://doi.org/10.1109/cpem.2016.7540802
2016-01-01
Abstract:The paper presents the development of a 35 kV fully-insulated two-stage voltage transformer(TSVT), and its applications by connecting in series with another 35 kV semi-insulated TSVT to determine the voltage dependence(VD) of a 110 kV TSVT. The result showed the VD of the 110 kV TSVT is around -1.6×10 -6 and +1.6 μrad in magnitude and phase, respectively.