Transient-steady State Vibration Characteristics and Influencing Factors under No-Load Closing Conditions of Converter Transformers
Peiyu Jiang,Zhanlong Zhang,Zijian Dong,Yu Yang,Zhicheng Pan,Fanghui Yin,Menghao Qian
DOI: https://doi.org/10.1016/j.ijepes.2023.109497
2022-01-01
SSRN Electronic Journal
Abstract:The converter transformer plays a key role in the HVDC transmission project. It will be put back into the power grid after a power outage for maintenance. The transient overvoltage and excitation inrush current during charging and closing will cause shock vibration and affect the stability of the internal mechanical structure. In addition, the on-load tap-changer (OLTC) shifting operation after closing will also lead to changes in the vibration characteristics. Because of insufficient research on vibration during closing transient and no-load operation, this paper measures the transient vibration change process during no-load closing and tap-changer action in a +/- 800 kV converter station. Furthermore, the influence of voltage and winding turns changes on no-load vibration is also analyzed, and multi-characteristic parameters of vibration impulse factor, offset factor, and odd-even harmonic ratio are extracted to realize no-load state identification. The results show that the noload vibration increases with the increase of the voltage, and decreases with the increase of the number of turns of the grid-side winding. More importantly, both the charging closing and the tap-changer action will produce vibration and shock components, and the maximum transient vibration exceeds 90 m/s2, which is 35.7 times that of the steady-state. Odd harmonic components of 50 Hz, such as 150 Hz, 250 Hz, etc., will appear in the vibration spectrum under the action of the 2nd, 4th, and other even harmonics in the excitation inrush current. While the non-excitation inrush current is mainly an even multiple of 50 Hz. The research results reveal the vibration characteristics of the converter transformer during closing transient and no-load operation, and provide a theoretical reference for the evaluation and identification of the converter transformer under all operating conditions.