Optimal design of tower footing device with combined vertical and horizontal grounding electrodes under lightning

jinpeng wu,bo zhang,jinliang he,rong zeng
DOI: https://doi.org/10.1016/j.epsr.2014.03.021
IF: 3.818
2014-01-01
Electric Power Systems Research
Abstract:•The practical effects of driven rods on reducing the impulse impedance of the tower footing device are compared.•The non-metal driven rod takes the best effect while the metal driven rod takes the worst in the testing condition.•We analyzed the regularity of the optimal design of the tower footing device by numerical simulation.•The shorter the leg length and the higher the soil resistivity, the more likely to install the driven rod at the terminal.•With soil resistivity increasing or total length decreasing, optimal structure shall consist of fewer and longer electrodes.