Shafting Torsional Protection System at Shangdu Power Plant

Da-yu CHEN,Yong-lin ZHAO,Quan LIU,Yuan-qu ZHANG,Xiao-rong XIE
DOI: https://doi.org/10.3969/j.issn.1674-3415.2010.06.030
2010-01-01
Abstract:A subsynchronous torsional protection scheme is developed to protect generator shafts from damage caused by subsynchronous resonance(SSR).The scheme is composed of the bottom-layered torsional stress relay(TSR) and the upper-layered coordinator,called Tmaster.The TSR gathers the modal speed of generator shafts in real time and detects dangerous SSR according to the criteria of torsional stability and fatigue loss-of-life.The Tmaster coordinates the response from multiple TSRs and trips generators selectively.The proposed TSR+Tmaster scheme is implemented for the Shangdu series-compensated transmission system,of which the operation principle and the protection setting are elaborated in this paper.Since it was put into practice in September 2008,the protection system has experienced various field tests and real system faults,demonstrating its effectiveness in detecting subsynchronous vibration and protecting generator shafts.
What problem does this paper attempt to address?