The Solution to SSR Problem in Shangdu Series Compensation Transmission System

李国宝,张明,郭锡玖,李英伟,谢小荣,刘世宇
DOI: https://doi.org/10.3969/j.issn.1004-9649.2008.05.015
2008-01-01
Abstract:A scheme based on supplementary excitation damping control and torsional stress relay was presented and studied to handle the potential SSR problem in the second phase of Shangdu transmission system. Eigenvalue analysis and electromagnetic simulation was conducted to verify its effectiveness. The results show that SEDC can greatly improve the damping of the three concerned torsional modes and thus effectively depress SSR under normal operation conditions and following most short-circuit faults. For few extremely rarely occurring serious faults, TSR, as a protection measure, can initiate generator-trip action to ensure the stability of the system and the safety of the shafts. The SEDC and TSR based scheme proposed is an effective, economical and practicable solution to the SSR problem in the Shangdu series compensation transmission system.
What problem does this paper attempt to address?