Field Test of SEDC for Subsynchronous Torsional Damping Enhancement at Shangdu Power Plant

郭锡玖,谢小荣,刘世宇,李国宝,李英伟
DOI: https://doi.org/10.3321/j.issn:1000-1026.2008.10.022
2008-01-01
Abstract:A field test was conducted on the number 4 turbine-generator at Shangdu Power Plant to validate the effectiveness of supplementary excitation damping control (SEDC) for torsional damping enhancement. The principle, operating-condition, procedures and results of the test are presented. The test results indicate that torsional oscillation can be successfully and safely excited by injecting subsynchronous signals into the generator exciter regulator, and that SEDC greatly improves the torsional damping without interfering the AVR/PSS function. This is the first time in China that a practical SEDC has been developed and its effectiveness in improving torsional damping has been verified in the real system. It represents an important step toward application of SEDC for the purpose of SSO/SSR mitigation in China.