Abstract:Accurate calculation of fault current and fault voltage is the foundation of thermo-stabilization verification of compound optical ground wire and selection of the insulating gap of the ground wire. We established a phase-coordinate model of a finite length power line considering the mutual inductance between phase wires and ground wires,then simulated the transient current and the transient voltage process on the OPGW when the single phase to ground wire fault occurs at several different places. Results show that the peak value of the transient current is 1.3~1.7 times the steady current, and the peak value of the transient voltage is 1.1~1.6 times the steady voltage; the transient process lasts for 0.04~0.08 s; there is a quite big transient current and transient voltage value within the distance of 8kin to the fault point.