Analysis of Electrical Characteristics for Ground Wire Insulator and Parallel Gap

Zhenpeng Tang,Chengzhi Ma,Weiling Ye,Lingzi Zhou,Yupu Sun,Fanghui Yin,Liming Wang
DOI: https://doi.org/10.1109/ceidp50766.2021.9705396
2021-01-01
Abstract:Currently, the abnormal discharge of the ground wire insulator occurs frequently in the overhead ground wire. In order to solve the insulation coordination problem of ground wire insulator and the parallel gap, the characteristics of ground wire insulator is investigated in this paper to select the appropriate parallel air gap distance. The results show that both the power frequency breakdown voltage and lightning breakdown voltage U50% of the ground wire insulator without the parallel air gap follow the power function relation with the ESDD. In addition, when the parallel air gap distance is the same, both the power frequency breakdown voltage and the lightning breakdown voltage of the suspension ground wire insulator and tension ground wire insulator are almost the same. According to the test results, when ESDD is 0.01 mg/cm2, 0.03 mg/cm2, 0.05 mg/cm2, 0.1 mg/cm2, 0.2 mg/cm2, the maximum gap distance can be set to 50 mm, 45 mm, 35 mm, 30 mm, 25 mm, respectively.