Analysis of the Lightning Overvoltage in the Power Cables of the DC Electric Traction System for the Electrified Railway in Hongkong

Qibin ZHOU,Xiaoyan BIAN,Zhengcai FU
DOI: https://doi.org/10.3321/j.issn:1001-4632.2009.04.017
2009-01-01
Abstract:For the DC electric traction system of the electrified railway in Hongkong,the power system simulation program EMTP was used to study the lightning overvoltage in the power cables of the DC electric traction system.Based on analyzing the configuration of DC electric traction system,the circuit simulation models including the contact system,masts and other vertical conductors,insulators,arresters and the earthing electrodes were built respectively.With these models,a complete EMTP simulation model of the DC electric traction system was constructed.During the modeling process,the nonlinear ionization characteristic of soil and the flashover characteristic of insulators were taken into account.The traction system of a certain segment electrified railway in Hongkong was taken as an example.The lightning overvoltage in the cables installed in the cable trough was estimated for different lightning stroke positions.The risk of flashover on the cables and the influence of mast earthing resistance on the lightning overvoltage in cables were analyzed.It was suggested that low earth resistance would effectively reduce the lightning overvoltage in the power cables.
What problem does this paper attempt to address?