Study on High Frequency Two-Stage Pulse Tube Refrigeration at 35 K: Part Ⅱ. Experimental Verification

GAN Zhi-hua,FAN Bing-yan,CHEN Jie,XU Ting,WANG Ren-jie,QIU Li-min
DOI: https://doi.org/10.3785/j.issn.1008-973x.2009.08.019
2009-01-01
Abstract:For the requirements of detectors cooling at 35 K in space application, based on the calculation and analysis from the regenerator simulation software known as REGEN 3. 2, a self-designed two-stage Stirling-type pulse tube cryocooler (PTC) for 35 K with cold inertance tube and cold reservoir at the second stage was manufactured and tested. Experiments on the effects of charging pressure, frequency, input power on the performance of the second stage PTC were carried out. The optimum charging pressure of 1.26 MPa and the optimum frequency of 40 Hz for 35 K were obtained, which agreed well with the theoretical calculation. The lowest no-load temperature of 27.4 K with the charging pressure of 1. 26 MPa and the frequency of 45 Hz together with 135 W input power was obtained. The cooling power of 0.45 W at 35 K with the charging pressure of 1.36 MPa and the frequency of 40 Hz was also obtained with an input electric power of 205 W.