Novel Algorithm for Measuring Active and Reactive Power

HUANG Chun,JIANG Ya-qun
DOI: https://doi.org/10.3321/j.issn:0258-8013.2008.04.009
2008-01-01
Abstract:A digital algorithm is presented to measure electric powers in power system in the presence of harmonics.In the algorithm,active power and reactive power are estimated by extracting the d.c.component from instantaneous active power and reactive power,respectively.Based on windowed discrete Fourier transform and its inverse transform,a novel implement method of Hilbert transform is proposed to introduce a phase shift of 90 degree for all frequency components of voltage signal.A comb digital filter,whose impulse response is a new rectangle self-convolution window,is designed to eliminate fundamental and harmonic components from instantaneous powers;therefore,the algorithm is characterized by high accuracy even at asynchronous sampling.At last,simulation results are examined to show the performance of the proposed algorithm.
What problem does this paper attempt to address?