THE PARAMETER ANALYSIS OF THE EFFECT OF UTILIAING THE THERMAL INSULATION COATINGS TO DECREASE BUILDING COOLING LOAD

Bin Xu,Hong Ye,Xinshi Ge,Dongsheng Jiao,Shuangyong Zhuang
DOI: https://doi.org/10.3321/j.issn:0254-0096.2006.09.001
2006-01-01
Abstract:A steady state heat transfer model was constructed to simulate the effect of the thermal insulation coatings (TICs) on the building cooling load. The influences of the TICs parameters, such as the thermal conductivity, thickness, solar absorptivity, emissivity, and the ambient parameters, were analyzed numerically. It is found out that the cooling load could be decreased remarkably by the application of TICs to the building outer wall surface; only when the ratio of TICs' thermal resistance to the wall's is larger than 0.2, the TICs thermal conductivity can have a strong influence on the cooling load; TICs' surface solar absorptivity and emittance are the dominant factors to the cooling load; the function of the TICs is distinct in the regions with more intensive solar radiation, lower outdoor diurnal top air-temperature and larger diurnal range of temperature, and in thus regions a higher energy conservation rate and lower diurnal energy consumption could be obtained by using TICs; the distribution of the local outdoor air-temperature which determine the air-conditioning running time has important influence on the evaluating of the energy conservation effects of the TIC.