IMPACT OF BUILDING OUTSIDE WALL THERMAL INERTIA ON AIR CONDITIONING COOLING LOAD

Bai Xuelian,Zhang Zaixi,Li Wenlong
2013-01-01
Abstract:This article selected the residential building in Chongqing as the research object.By changing the external wall insulation materials,nine kinds of exterior walls had been constructed,which had different heat storage performance but same transfer coefficient.It was calculated the building air conditioning cooling load by the eQUEST software and analyzed the influence of the thermal inertia on the cumulative load under different air conditioning running mode.The results showed that the effect of the thermal inertia index on the air conditioning cooling load was not significant when the thermal inertia index is less than 3.The increase of the thermal inertia index and attenuation multiple was beneficial to the decreasing of the accumulated cooling loads,but the extent of influence of the two parameters was changed.In addition,the effect of the thermal inertia index on the cumulative cooling load also need to consider the thermal performance requirements of different rooms in different times.