Single-end Fault Locating Considering Errors Due to Incomplete Decoupling of Unsymmetrical Lines

CHEN Jin-gen,XU Qing-shan,TANG Guo-qing
DOI: https://doi.org/10.3969/j.issn.1006-6047.2006.09.015
2006-01-01
Abstract:The singularity of traveling wave extracted by wavelet transform at different scales is used to accurately locate ultra-high voltage transmission line faults.For un-transposed lines,the traditional decoupling methods cannot eliminate the coupling among three phases completely,which brings difficulty in traveling wave surge detection.An unsymmetrical numerical decoupling method is presented and the actual wave velocity is introduced.Firstly,three-phase currents are decoupled by the phase-model transformation.Considering the uniform transposition and un-transposition or incomplete transposition of three-phase transmission lines,the transformation matrix is determined and then used to calculate the inductance and capacitance parameters.The single-terminal fault location method is applied,and the wavelet transform is used to detect the singularity signal,thus the traveling wave signal analysis is transformed to modulus maxima analysis.Simulation results show that the method can decouple each phase efficiently and the precision is greatly increased compared with the method using symmetrical presupposition.
What problem does this paper attempt to address?