A NEW ALGORITHM BASED ON THE DISTRIBUTION OF THE NORMALIZED EQUIVALENT INSTANTANEOUS INDUCTANCE FOR THE DISCRIMINATION OF INRUSH

ZHENG Tao,LIU Wan-shun,Zhuang Heng-jian,LI Xiao-bo
DOI: https://doi.org/10.3321/j.issn:0258-8013.2005.23.009
2005-01-01
Abstract:Oriented to wye-delta connected three phase transformer, a new configuration of current transformer (CT) in transformer differential protection is proposed. In this configuration, only one single phase CT connected in any phase of the delta side is more needed than the traditional scheme. Worked with line currents measured by other current transformers connected in both sides of the transformer, any phase current in the delta side can be calculated based on the Kirchhoff's Current Law. This new scheme ensures the accurate calculation of the equivalent instantaneous inductance, which is immune to the loop current existed in the delta side of transformer, as well as no dead zone in transformer differential protection. A new algorithm based on the distribution of the normalized equivalent instantaneous inductance for the discrimination between inrush current and fault current is proposed. The normalization of equivalent instantaneous inductance makes the setting-value have little relation with the parameter of transformers, which has more universal meaning in the determination of setting values. Utilizing the distributive characteristic of the normalized equivalent instantaneous inductance, the variety of the normalized equivalent instantaneous inductance is effectively revealed. At last, experiment data obtained from HYBRISIM (Hybrid Simulator) validates the reliability and sensitivity of this algorithm. This algorithm has good prospect of engineering application in the EHV transformer protection.
What problem does this paper attempt to address?