A Novel Scheme to Fast Discriminate Inrush Current from Internal Fault of Power Transformer

L(U) Zhi-juan,LIU Wan-shun,XIAO Shi-wu,ZHENG Tao
DOI: https://doi.org/10.3321/j.issn:0258-8013.2006.02.009
2006-01-01
Abstract:A new algorithm based on waveform characteristics is presented for fast discrimination between inrush current and fault current of power transformers. The method is based on that the waveform of inrush current (concave) distorts seriously, while the fault current nearly keeps sinusoid (convexity). Utilizing the sample data within 5 ms after fault initiation and extending the data windows from 5 ms to 10 ms, the approximate current formula can be extracted from fault current or inrush current using least square fitting method. According to the curvature and convex-concave characteristic of the fitting curve, inrush current and fault current of power transformers can be distinguished. Experimental results indicate that this algorithm is not only effective under various fault conditions but also can be realized easily and hardly to be affected by current transformer saturation and decaying DC components. Moreover, fault clearance time can be limited within 5 ms.
What problem does this paper attempt to address?