IDENTIFICATION OF LIGHTNING AND FAULT IN EHV TRANSMISSION LINE TRANSIENT-BASED PROTECTION

段建东,张保会,郝治国,哈恒旭
DOI: https://doi.org/10.3321/j.issn:1000-1026.2004.18.006
2004-01-01
Abstract:It is difficult to reliably identify lightning disturbance from a fault in transmission lines. The lightning disturbance includes inductive lightning and mild direct-lightning surges that do not cause any fault, and the state of fault involves general faults and severe direct-lightning surges that can cause short-circuit. This paper first analyzes various lightning waves and fault traveling-waves to find the waveform features and magnitude relation among modulus traveling-waves. The characteristics are as follows: the aerial-mode components are far less than ground-mode component of three-phase lines in the case of inductive lightning; the sudden-change occurs abruptly at both the front and chopped wave in severe direct-lightning waveform; the duration of mild direct-lightning is shorter than that of the fault traveling-wave. Then the paper proposes the principle and the wavelet-transform-based algorithm for identifying inductive lightning, mild/severe direct-lightning and general faults. A number of EMTP simulation tests show that the novel identification method is feasible and reliable.
What problem does this paper attempt to address?