Characteristics of Induced Overvoltage Generated by Triggered Lightning in the Low Voltage Power Supply System

CHEN Shao-dong,ZHANG Yi-jun,YANG Shao-jie,DONG Wan-sheng,WANG Jian-guo,L(U) Wei-tao,WANG Xiao-bo
DOI: https://doi.org/10.13336/j.1003-6520.hve.2009.12.025
2009-01-01
Abstract:The lightning protection on the power system of electronic equipment was tested,as AWSs collectors nationwide have been frequently struck by lightning and failed to operate normally.Using the artificially triggered lightning techniques,the induced effects caused by the lightning and the key lightning protection techniques research were developed near the lightning channel.The induced overvoltage characteristics and SPD residue voltage characteristics caused by triggered lightning with multiple return strokes on the transmission line of an AWS,as well as the relationship with the triggered lightning,were analyzed.The results show that:(a) The return strokes of the near triggered lightning generate bipolar induced overvoltages on the overhead line,with peaks up to more than 10 kV.The overvoltages can be divided into the main peak phase and the subsequent overvoltage phase,which last about 100μs and 4ms respectively on average.The period of the subsequent overvoltages is related to the fluctuation of the continuous current behind return stroke of the triggered lightning;(b) Overvoltages of 2 kV or above can be induced at the initial continuous current phase.They last a long period of time and concentrate about 12ms,with the mean voltage being 332.5V.Its potential damage to the transmission line cannot be neglected.Residue voltages of SPD play an effect on limiting voltage and releasing current in a degree with stable performance,and there is positive correlation between its peak value and peak current of triggered lighting,the correlation coefficient is 0.86.
What problem does this paper attempt to address?