Observation of Induced Voltage at the Terminal of 10 kV Distribution Line by Nearby Triggered Lightning

Jianguo Wang,Shoupeng Wang,Li Cai,Dai Lu,Quanxin Li,Mi Zhou,Yadong Fan
DOI: https://doi.org/10.1109/tpwrd.2019.2958182
IF: 4.825
2020-08-01
IEEE Transactions on Power Delivery
Abstract:This paper presents the induced voltage measured at the terminal of a 10 kV distribution line when triggered lightning taking place at a distance of 40 m. It is shown that the induced voltage waveforms exhibit three components including a slow increase preceding the initial negative peak, following a rapid polarity reversal and the attenuated oscillations. The waveform parameters are defined in this paper. The observed negative peak value ranges from −47.1 kV to −7.5 kV. The positive peak value ranges from 5.3 kV to 20.9 kV, and the peak to peak value ranges from 12.8 kV to 63.2 kV. The test results show that the negative peak value of the induced voltage at the terminal of distribution generated by nearby negative triggered lightning generally exceeds the positive peak value, and in some cases the negative peak value even reaches twice the positive peak value. The negative 10%-90% rise time ranges from 2.3 μs to 88.5 μs, and the average oscillation period is about 18 μs. Both negative and positive peaks of induced voltages show good linear relationship with the peaks of lightning return stroke current.