Experimental Study and Industrial Application of Flue Gas Suspension Desulfurization Facility with Dual Circulating Fluidized Bed

董勇,马春元,秦裕琨
DOI: https://doi.org/10.3321/j.issn:1006-8740.2003.06.010
2003-01-01
Abstract:The flue gas suspension desulfurization process with dual circulating fluidized bed was proposed in this study.The process is composed of dual separating facility—inner inertia separator and outer cyclone separator with downward exhaust gas.The resistance characteristics,SO_2 removal and drying performances were obtained from the experimental study carried out in a 3 000 m~3/h pilot scale test unit.The process has been industrially applied in the 75 t/h boiler in a thermal power station.It is shown that SO_2 removal of 92% is achieved at Ca/S=1.3,AAST=8 ℃,and the drying time of slurry is approximately 1.5—2.0 s,the resistance drop is 1 kPa.
What problem does this paper attempt to address?