AC Flashover Performance and Mechanism of Polluted and Iced IEC Standard Suspension Insulator String

CX Sun,XL Jiang,LC Shu,Z Lu,MY Chen
2003-01-01
Abstract:Based on a series of systematic laboratory investigation carried out on the flashover of strings of 3, 6 and 9 ice-covered IEC standard suspension insulator units, this paper discusses the flashover performance and process. And it is put forward that the product sigma(0) of the icing water conductivity gamma(20) converted to the value of 20degreesC by the average ice amount w accreted on an insulator unit could be used as a characteristic parameter to show the effect of the ice and the contamination contaminated icing water as well as the pre-contamination of the insulator on the flashover voltage. And the process of AC partial arcs of the iced insulator string coming-into-being, developing, extinguishing and re-igniting was discussed in the paper. And it indicates that the minimum flashover voltage of string of ice-covered IEC standard suspension insulator units is direct proportional to the units or length of an insulator string.
What problem does this paper attempt to address?